Product Name | LMZ Series low voltage Current transformer |
P/N | MLBH-2148 |
Installation Method | Vertical or horizontal |
Rated Voltage | 0.5kV,0.66kV, |
Rated power factor | COSφ=0.8 |
Rated Secondary Current | 5A 、1A |
Insulation withstand voltage | 3KV/60S |
Operating Frequency | 50 or 60Hz |
Ambient Temperature | -5℃ ~ +40℃ |
Ambient relative humidity | ≤ 80% |
Altitude | Less than 1000m |
Terminal Marks | P1、P2 is primary polarity end;S1、S2 is Secondary polarity end |
Application | Power system for current and energy protect |
Vertical or horizontal mounting of the transformer
High accuracy, low voltage, long life time
This transformer‘s precision is much higher than plastic case type.
P/N |
Rated primary current(A) |
Rated turns ratio |
Accuracy and rated secondary burden (VA) |
||||
0.5S |
0.2 |
0.5 |
1 |
5P6 |
|||
LMZ1-0.5 |
5,10,20,25,50,100 |
100 |
5 |
5 |
5 |
5 |
- |
15,30,40,60 |
120 |
||||||
75,150 |
150 |
7.5 |
|||||
200 |
200 |
||||||
250 |
250 |
||||||
300 |
300 |
||||||
400 |
400 |
||||||
LMZJ1-0.5 |
5,10,15,20,25,30,50,60,75,100,150,300 |
300 |
5 |
10 |
15 |
- |
|
250 |
250 |
||||||
40,200,400 |
400 |
||||||
500 |
500 |
10 |
|||||
600 |
600 |
||||||
750 |
750 |
||||||
800 |
800 |
||||||
1000 |
1000 |
10 |
15 |
20 |
30 |
10 |
|
1200 |
1200 |
||||||
1500 |
1500 |
||||||
2000 |
2000 |
||||||
2500 |
2500 |
||||||
3000 |
3000 |
||||||
4000 |
4000 |
P/N |
Rated primary current(A) |
Rated turns ratio |
Rated output(VA) |
|||
0.2 |
0.5s |
0.5 |
1 |
|||
LMZ1-0.66 LMZ2-0.66 |
150-400 |
100 |
/ |
5 |
5 |
5 |
500-800 |
120 |
5 |
5 |
10 |
10 |
|
1000-1250 |
150 |
10 |
10 |
15 |
20 |
|
LMZ2-0.66 |
1500 |
300 |
||||
2000-3000 |
250 |
15 |
15 |
20 |
25 |
|
4000 |
400 |
30 |
30 |